Product Details
Place of Origin: Hefei Anhui China
Brand Name: FeiChun™
Certification: AS/NZS 2802:2000 AS/NZS 1125:2001 And AS/NZS 2802:2003
Model Number: FeiChun 2000919
Payment & Shipping Terms
Minimum Order Quantity: 200 Meter
Price: Please Contact Our Sales Engineer
Packaging Details: Cable Reels or Packaging Bags
Delivery Time: 15-30 Days
Payment Terms: T/T, Western Union
Supply Ability: Please Contact Our Sales Engineer According To The Specific Model
Armor Type: |
Steel Wire Armor |
Flexibility: |
Extra Flexible |
Grounding Features: |
Includes Grounding For Added Safety |
Standard: |
IEC 60502-1 |
Voltage: |
Medium Voltage |
Voltage Rating: |
15KV |
Armor Type: |
Steel Wire Armor |
Flexibility: |
Extra Flexible |
Grounding Features: |
Includes Grounding For Added Safety |
Standard: |
IEC 60502-1 |
Voltage: |
Medium Voltage |
Voltage Rating: |
15KV |
Elevate Your Mining Efficiency with Cutting-Edge Technology
In the demanding world of mining, where reliability and performance are non-negotiable, the EPR PCP High Voltage Fiber Optic Reeling Cable F-(N) TSCGEWÖU stands out as a revolutionary solution.
This advanced cable is designed to meet the rigorous requirements of modern mining operations, integrating high voltage capabilities with state-of-the-art fiber optic technology.
Engineered with a blend of high-performance materials and produced to German standards, this cable sets a new benchmark for durability and functionality in the industry.
Conductors | Flexible stranded copper conductor, class 5 according to DIN VDE 0295. |
Inner Conductor Layer | Semi-conductive layer. |
Insulation | EPR type 3GI3. |
Outer Conductor Layer | Semi-conductive layer. |
Earth Conductor | Split into two in the outer interstices. |
InnerSheath | Rubber type GM1b/5GM3. |
Fiber Optics | 12 FO 50/125 or 62.5/125 or E9/125μm within protection sheath. |
Reinforcement | Polyester anti-torsion braid |
Outer Sheath | Rubber type 5GM3/5GM5, flame retardant and oil resistant. |
The EPR PCP High Voltage Fiber Optic Reeling Cable F-(N) TSCGEWÖU is crafted using a combination of specially formulated materials, including CPE (Chlorinated Polyethylene), EPR (Ethylene Propylene Rubber), PCP (Polychloroprene), and Kevlar.
Each material is selected for its unique properties, contributing to the overall strength and structural robustness of the cable:
CPE provides excellent resistance to chemicals, oils, and weather conditions, ensuring the cable’s longevity in harsh mining environments.
EPR offers superior insulation and flexibility, essential for high voltage applications and to withstand the physical stresses of reeling.
PCP enhances the cable’s durability against abrasion and mechanical stress, extending its service life.
Kevlar, known for its use in bulletproof vests, significantly boosts tensile strength, allowing the cable to handle high tension without compromising performance.
This combination of materials ensures that the F-(N) TSCGEWÖU cable remains intact and performs reliably, even under extreme conditions.
The cable's high voltage capability is a key feature, ensuring that it can handle demanding electrical requirements in mining operations.
The robust design and high-quality materials used in its construction enable it to deliver consistent power transmission, making it suitable for various mining machinery and equipment. This reliability is crucial for maintaining operational efficiency and safety in high-stress environments.
One of the standout features of the F-(N) TSCGEWÖU cable is its incorporation of optical fibers.
This integration transforms the cable from a standard high voltage solution into a cutting-edge technology capable of supporting advanced data communication systems.
The addition of fiber optics allows for:
Real-Time Data Transmission: High-speed data transfer enables real-time monitoring and control of mining operations. This is essential for the effective management of machinery and equipment.
Enhanced Automation: The integration of optical fibers supports the advancement of unmanned automation systems. This leads to increased efficiency and safety, as operations can be monitored and controlled remotely.
Improved Communication: The cable facilitates reliable communication between different parts of a mining operation, enhancing coordination and reducing downtime.
The F-(N) TSCGEWÖU cable is produced and tested in accordance with stringent German standards. Germany is renowned for its high engineering and manufacturing standards, and this cable adheres to those exacting requirements.
Quality Assurance: Every cable undergoes rigorous testing to meet safety and performance standards, ensuring it performs reliably in real-world conditions.
Safety Compliance: Adherence to these standards guarantees that the cable meets all relevant safety requirements, reducing the risk of electrical failures and hazards.
Versatile Applications in Mining
The EPR PCP High Voltage Fiber Optic Reeling Cable F-(N) TSCGEWÖU is designed for use in a wide range of mining applications. Its high voltage capabilities and fiber optic integration make it suitable for:
Mining Machinery: The cable can be used with various types of mining equipment, including drills, loaders, and continuous miners.
Reeling Systems: Its flexibility and durability make it ideal for reeling systems, where it must withstand constant movement and tension.
Underground Operations: The cable’s robustness and resistance to environmental factors make it suitable for underground mining environments, where conditions are harsh and challenging.
The materials used in the F-(N) TSCGEWÖU cable are selected for their exceptional properties:
Flexibility and Strength:
The combination of EPR and PCP materials ensures that the cable remains flexible and strong, even under high tension.
Chemical and Abrasion Resistance:
CPE and PCP provide resistance to chemicals and abrasion, extending the cable's lifespan and reducing maintenance needs.
Tensile Strength:
Kevlar enhances the cable’s tensile strength, allowing it to handle high loads without failure.
Installing and maintaining the EPR PCP High Voltage Fiber Optic Reeling Cable is straightforward due to its flexibility and durability. The cable’s ability to handle constant reeling and unwinding reduces the risk of damage and makes it easier to manage during installation.
Its high-quality construction also means fewer maintenance issues, leading to lower overall costs and increased operational efficiency.
The EPR PCP High Voltage Fiber Optic Reeling Cable F-(N) TSCGEWÖU is a premier choice for mining operations requiring both high voltage and advanced data communication capabilities. With its robust construction, high performance, and compliance with German standards, this cable delivers exceptional reliability and functionality.
The integration of fiber optics supports the future of unmanned automation, providing a competitive edge in the industry. Invest in the F-(N) TSCGEWÖU cable and experience enhanced efficiency, safety, and technological advancement in your mining operations.
F-(N) TSCGEWÖU EPR PCP HIGH VOLTAGE REELING CABLE TECHNICAL DATA
Standards | DIN VDE 0250, Part 813 | ||||||
Rated voltage (Uo/U) | 1.8/3 | 3.6/6 | 6/10 | 8.7/15 | 12/20 | 14/25 | 18/30 |
Maximum permissible operating voltage in AC systems (Uo/U) | 2.1/3.6 | 4.2/7.2 | 6.9/12 | 10.4/18 | 13.9/24 | 17.3/30 | 20.8/36 |
Maximum permissible operating voltage in DC systems (Uo/U) | 2.7/5.4 | 5.4/10.8 | 9/18 | 13.5/27 | 18/36 | 22.5/45 | 27/54 |
AC test voltage According to DIN VDE 0250, Part 813 | 6 | 11 | 17 | 24 | 29 | 36 | 43 |
Current carrying capacity | According to DIN VDE 0298, Part 4 Higher values are permissible in specific cases.Please consult the manufacturer. |
No. of coresx cross-section | Outer-Ø ca. mm. | Copper weight | Cable weight approx. | Tensile strength | AWG |
n x mm2 | ± 10% | kg/km | kg/km | N | no.*) |
3.6/6 (7.2) kV F-NTSCGEWÖU OF | |||||
3×25+2×25/2+6LWL | 38.2 | 960 | 2635 | 1125 | 4 |
3×25+2×50/2+6LWL | 42.1 | 1200 | 3070 | 1125 | 4 |
3×35+2×25/2+6LWL | 42 | 1248 | 3055 | 1575 | 2 |
3×35+2×50/2+6LWL | 43.8 | 1488 | 3418 | 1575 | 2 |
3×50+2×25/2+6LWL | 45.3 | 1680 | 3503 | 2250 | 1 |
3×50+2×50/2+6LWL | 45.3 | 1920 | 3630 | 2250 | 1 |
3×70+2×25/2+6LWL | 48.5 | 2256 | 4340 | 3150 | 2/0 |
3×70+2×50/2+6LWL | 51.7 | 2496 | 5270 | 3150 | 2/0 |
3×95+2×50/2+6LWL | 54.2 | 3216 | 5540 | 4275 | 3/0 |
3×120+2×70/2+6LWL | 57.9 | 4128 | 7032 | 5400 | 4/0 |
3×150+2×70/2+6LWL | 63 | 4992 | 8010 | 6750 | 250MCM |
3×185+2×95/2+6LWL | 66 | 6240 | 9320 | 8325 | 350MCM |
3×240+2×120/2+6LWL | 74.1 | 8064 | 11930 | 10800 | 450MCM |
3×300+2×150/2+6LWL | 79.3 | 10080 | 14215 | 13500 | 550MCM |
6/10 (12) kV F-NTSCGEWÖU OF | |||||
3×25+2×25/2+6LWL | 42.9 | 960 | 2515 | 1125 | 4 |
3×25+2×50/2+6LWL | 44.6 | 1200 | 2945 | 1125 | 4 |
3×35+2×25/2+6LWL | 45.1 | 1248 | 2975 | 1575 | 2 |
3×35+2×50/2+6LWL | 46.2 | 1488 | 3340 | 1575 | 2 |
3×50+2×25/2+6LWL | 46.6 | 1680 | 3630 | 2250 | 1 |
3×50+2×50/2+6LWL | 48.3 | 1920 | 3790 | 2250 | 1 |
3×70+2×25/2+6LWL | 49.9 | 2256 | 4515 | 3150 | 2/0 |
3×70+2×50/2+6LWL | 54.7 | 2496 | 4740 | 3150 | 2/0 |
3×95+2×50/2+6LWL | 55.5 | 3216 | 5720 | 4275 | 3/0 |
3×120+2×70/2+6LWL | 59.2 | 4128 | 6875 | 5400 | 4/0 |
3×150+2×70/2+6LWL | 64.3 | 4992 | 8215 | 6750 | 250MCM |
3×185+2×95/2+6LWL | 68.3 | 6240 | 9518 | 8325 | 350MCM |
3×240+2×120/2+6LWL | 75.4 | 8064 | 12185 | 10800 | 450MCM |
3×300+2×150/2+6LWL | 80.6 | 10080 | 14522 | 13500 | 550MCM |
14/25 (30) kV F-NTSCGEWÖU OF | |||||
3×25+2×25/2+6LWL | 52.3 | 960 | 3740 | 1125 | 4 |
3×25+2×50/2+6LWL | 52.3 | 1200 | 3900 | 1125 | 4 |
3×35+2×25/2+6LWL | 55.1 | 1248 | 4270 | 1575 | 2 |
3×35+2×50/2+6LWL | 55.1 | 1488 | 4440 | 1575 | 2 |
3×50+2×25/2+6LWL | 58.3 | 1680 | 5000 | 2250 | 1 |
3×50+2×50/2+6LWL | 58.3 | 1920 | 5160 | 2250 | 1 |
3×70+2×25/2+6LWL | 63 | 2256 | 6190 | 3150 | 2/0 |
3×70+2×50/2+6LWL | 63 | 2496 | 6390 | 3150 | 2/0 |
3×95+2×50/2+6LWL | 67.3 | 3216 | 7340 | 4275 | 3/0 |
3×120+2×70/2+6LWL | 71 | 4128 | 8550 | 5400 | 4/0 |
3×150+2×70/2+6LWL | 76 | 4992 | 10020 | 6750 | 250 MCM |
3×185+2×95/2+6LWL | 79 | 6240 | 11410 | 8325 | 350 MCM |
3×240+2×120/2+6LWL | 87.5 | 8064 | 14380 | 10800 | 450 MCM |
3×300+2×150/2+6LWL | 92.7 | 10080 | 16820 | 13500 | 550 MCM |
18/30 (36) kV F-NTSCGEWÖU OF | |||||
3×25+2×25/2+6LWL | 55.7 | 960 | 4140 | 1125 | 4 |
3×25+2×50/2+6LWL | 55.7 | 1200 | 4310 | 1125 | 4 |
3×35+2×25/2+6LWL | 58.6 | 1248 | 4720 | 1575 | 2 |
3×35+2×50/2+6LWL | 58.6 | 1488 | 4880 | 1575 | 2 |
3×50+2×25/2+6LWL | 63.2 | 1680 | 5680 | 2250 | 1 |
3×50+2×50/2+6LWL | 63.2 | 1920 | 5840 | 2250 | 1 |
3×70+2×25/2+6LWL | 66.6 | 2256 | 6670 | 3150 | 2/0 |
3×70+2×50/2+6LWL | 66.6 | 2496 | 6870 | 3150 | 2/0 |
3×95+2×50/2+6LWL | 70.7 | 3216 | 7860 | 4275 | 3/0 |
3×120+2×70/2+6LWL | 75.8 | 4128 | 9350 | 5400 | 4/0 |
3×150+2×70/2+6LWL | 79.5 | 4992 | 10630 | 6750 | 250 MCM |
3×185+2×95/2+6LWL | 82.5 | 6240 | 12040 | 8325 | 350 MCM |
3×240+2×120/2+6LWL | 91 | 8064 | 15070 | 10800 | 450 MCM |
3×300+2×150/2+6LWL | 97.2 | 10080 | 17780 | 13500 | 550 MCM |
Note: This is just part of the standard parameters of our products. Please contact our Engineer if you need more. And the information contained within this webpage is for guidance only and is subject to change without notice or liability. All dimensions and specifications are nominal and are subject to normal manufacturing tolerances. All pictures shown are for illustration purposes only. The actual product may vary. All the information is provided in good faith and is believed to be correct at the time of publication.